Control Centre RWZ 5f-E

This SHEVS Control Centre allows the configuration of one SHE group and one or two ventilation groups. 24 V= actuators can be controlled with a total output current of 10 or 20 A.

In addition to the DIP switches for setting the desired functions, the control centre has an internal service display that shows operating states as well as alarm and fault messages. Furthermore, coloured LEDs indicate active travel commands and other operating modes. The status of the SHEV system can thus be checked at the control centre in a user-friendly way.

Choose the preferred output voltage and output current in the dropdown menu. You can find compatible accumulators and options under “Accessories”.

    Description

    The SHEVS Control Centre RWZ 5f-E delivers a total output current of up to 10 or 20 A, depending on the version, and has three signalling lines. It allows the configuration of one SHE group and of one or two ventilation groups. Several functions can be set via DIP switches.

    Besides the detectors, ventilation buttons with indication of position and an external wind and rain control of the type WRS are connectable. As an alternative, the option WRM is available as internal wind and rain control.


    General information about SHEVS and Control Centres

    A smoke and heat exhaust system is an integral part of a fire protection system. Since by far the most fire victims are due to asphyxiation, smoke and heat exhaust ventilation systems make a decisive contribution to saving human lives.
    The simultaneous opening of windows and flaps at the bottom and top of buildings ensures that fresh air can flow into the building at the bottom and smoke and toxic fumes can flow out of the building at the top.
    Since they form part of a safety system, our products must meet the highest standards. To ensure that the system functions reliably even in the event of a mains failure, accumulators provide the emergency power supply for at least 72 hours.

    Control centres form the centrepiece of a SHEV system. They offer numerous connection options for detectors, buttons, sensors and fire alarm control panels. All signalling lines are monitored for wire breakage and short circuits. The incoming signals are processed by the control centre and, depending on the configuration and programming, converted into travel commands, warning messages and fault messages.

    In addition to the life-saving function in the event of a fire, our control centres, controls and actuators are also suited for the natural ventilation in buildings. For the daily opening and closing of windows, roof flaps and domelights, our actuators are designed to be particularly low-noise, maintenance-friendly and durable.

    Technical Data

     

    Type RWZ 5f-E-10 RWZ 5f-E-20
    Part number 8101 5610 0000 8101 5620 0000
    Line voltage supply 230 V~/50 – 60 Hz 230 V~/50 – 60 Hz
    Output current 10 A (24 V=/240 W) 20 A (24 V=/480 W)
    Number SHE groups 1 1
    Number ventilation groups 2 2
    Accumulators (AGM, VRLA), VdS approved 2 x 7 Ah/12 V 2 x 12 Ah/12 V
    Internal supply voltage 24 V=/72 h in case of mains failure 24 V=/72 h in case of mains failure
    Environmental class 1/III (EN 12101-10/VdS 2581) -5 °C … +40 °C -5 °C … +40 °C
    Relative humidity 20 % … 80 %, non-condensing 20 % … 80 %, non-condensing
    Enclosure protection rating IP30 IP30
    Dimensions (W x H x D) 400 x 490 x 125 mm 400 x 490 x 125 mm

    Approvals

    • Control unit desgined according to ISO 21927-9
    • Environmental class 1 (EN 12101-10/ISO 21927-9)/III (VdS 2581)