SHE Control IS 2

This SHEV control uses a 24 V= pulse output to control electromagnets/electrovalves (CA/CFR), pneumatic valves with electric components (EA/EZ) or pyrotechnic pressure gas generators (DG). The impulse control IS 2 enables the setting up of one SHE group and has two signal lines.

Two potential-free contacts are available for forwarding fault or alarm messages. One of the contacts can be wired to the internal 24 V= output for controlling external warning devices.

    Technical Data

    Type IS 2-4d IS 2-4d-SG
    Part number 8140 2404 0000 8140 2404 0002
    Line voltage supply 230 V~/50 – 60 Hz 230 V~/50 – 60 Hz
    Output current 3,75 A (24 V=/90 W) 3,75 A (24 V=/90 W)
    Number SHE groups 1 1
    Accumulators (AGM, VRLA), VdS approved 2 x 0,8 Ah/12 V 2 x 0,8 Ah/12 V
    Internal supply voltage 24 V=/72 h in case of mains failure 24 V=/72 h in case of mains failure
    Environmental class 1/III (EN 12101-10/VdS 2581) -5 °C … +40 °C -5 °C … +40 °C
    Relative humidity 20 % … 80 %, non-condensing 20 % … 80 %, non-condensing
    Enclosure protection rating IP40 IP54
    Dimensions (W x H x D) 165 x 155 x 75 mm 200 x 155 x 95 mm

    Downloads

    Documentation
    Approved accumulators

    Accessories

    Corresponding components: