Technical Data
- Response class CS according to EN 54-5
- Application temperature 55 – 80 °C
- Static reaction: 84 – 100 °C
- Nominal temperature 90 °C
- Operating voltage 9 – 33 V=
- Quiescent current input approx. 45 µA/24 V=
- Suitable for -20 to +90 °C, 10 to 95 % rel. humidity
- 100 mm diameter, flat design: with standard base only 50 mm, with relay base only 59 mm high