Technical Data
- Optical detection method according to EN 54-7:2000 with drift compensation as in RM 3-O
- Thermal detection method according to EN 54-5:2000. Response class A1R: Trigger temperature approx. 58 °C or temperature rise of 8 °C/min
- Max. detection height 7,5m
- Operating voltage 8 – 30 V=
- Quiescent current input approx. 65 µA/24 V=
- Current input during alarm approx. 50 mA/24 V=
- To be used for -30 to +70 °C. However, temperature range of 0 to +50 °C should not be exceeded for a longer time
- Relative humidity: 5 – 95 % (non-condensing)
- Air speed up to 20 m/s
- Dimensions including base MS 3-S: Ø102 x 55 mm